Product Details:
|
Product Name: | Chlorine Dioxide Transmitter | Product Model: | ADS2-U3A-CD10 |
---|---|---|---|
Software Version: | DRFN Chlorine Dioxide Analysis Software V1.0 | Display Range: | 0.00-200.00mg/L |
Protection Grade: | IP66 | Size: | 144*144*120mm |
Power Supply: | 100~240V AC | Weight: | 800g |
Power Consumption: | 12W | Mounting Method: | Wall Mount, Pipe Clamping, Panel |
Highlight: | 220V Water Quality Transmitter,IP66 chlorine dioxide sensor,800g Water Quality Transmitter |
220V Amperometric Chlorine Dioxide Transmitter For Drinking Water 800g
Introduction
A large number of experimental studies have shown that chlorine dioxide is a safe and non-toxic disinfectant with no "three-causing" effects (carcinogenic, teratogenic, and mutagenic). At the same time, it does not react with organic substances during the disinfection process.
The ADS2-U3A-CD10 chlorine dioxide analyzer water quality transmitter is a single parameter analyzer,specially used in the disinfection industry. Each chlorine dioxide instrument is connected to DRFN's chlorine dioxide sensors to realize the measurement of chlorine dioxide disinfectants.
Advantages Of Chlorine Dioxide Transmitter
1. The protection grade of the chlorine dioxide controller shell is IP66, which can effectively isolate the pollution and corrosive gas intrusion from the external environment.
2. All the configuration entered by the user is kept indefinitely, even if there is no power, the data will not be lost.
3. 128*64 black and white graphic dot matrix screen, and the display backlight provides always on and energy-saving mode selection.
4. It has time and historical data recording functions to meet higher data management requirements.
5. The user can use the operation panel on the front of the controller to calibrate the sensor and set various parameters that need to be output.
6. Two settable 0/4~20mA active current loop outputs, and each current output allows the user to specify what measurement value it represents.
7. The controller has two settable SPST relays. The setting objects include alarms for the high and low values of the measurement parameters, the control of the cleaning cycle of the sensor. The warning of the working environment temperature of the instrument.
Applications Of Chlorine Dioxide Transmitter
Online analysis of chlorine dioxide in municipal tap water, drinking water, food, beverages, and other water sources and water supply pipe networks;
Online analysis of circulating cooling water and swimming pool water, as well as sewage and wastewater disinfection and chemical addition control.
Parameters Of Chlorine Dioxide Transmitter
Product Name | Chlorine Dioxide Transmitter |
Product Model |
ADS2-U3A-CD10 |
Software Version |
DRFN chlorine dioxide Analysis software V1.0 |
Display Range |
0.00-200.00mg/L |
Resolution |
0.001 mg/L |
Accuracy |
Better than 0.15% of the measuring range |
Stability |
0.05% of the measuring range every 24 hours, no accumulation |
Repeatability |
Better than 0.1% of the measuring range |
Relay Control |
2 settable SPST relays, the max. load 3A/250VAC |
Sensor Self-diagnosis |
screen image and buzzer prompt |
Analog Current Output |
2 settable 0/4~20mA active current loop output max. load 1000Ω |
Communication Method |
RS485, MODBUS RTU; support JSON text data format |
Display Screen |
128*64 LCD |
Time History/Data Record |
Year/month/day/hour/min/second, record 14000 historical data |
Protection Grade |
IP66 |
Operating Environment |
0~60℃, relative humidity less than 95% |
Storage Environment |
-20~70℃, relative humidity less than 55% |
Shell Material |
Enhanced ABS |
Dimensions |
144*144*120mm (hole size 138*138 mm) |
Mounting Method |
Wall mounting, pipe clamping, panel installation |
Power Supply |
100~240V AC |
Weight |
800g |
Power Consumption | 12W |
Type |
Measuring range: ppm |
Resolution: ppm |
Output signal | Power supply | Item number |
CD10MA2 | 0.005~2.000 | 0.001 | 4~20 mA |
12~30 VDC RL 50Ω~900Ω
|
3426205 |
CD10MA5 | 0.05~5.00 | 0.01 | 3426206 | ||
CD10MA10 | 0.05~10.00 | 0.01 | 3426207 | ||
CD10MA20 | 0.05~20.00 | 0.01 | 3426208 | ||
CD10MA2-M12 |
0.005~2.000 |
0.001 |
3426230 |
||
CD10MA5-M12 |
0.05~5.00 |
0.01 |
3426231 |
||
CD10MA10-M12 |
0.05~10.00 |
0.01 |
3426232 |
||
CD10MA20-M12 |
0.05~20.00 |
0.01 |
3426233 |
Contact Person: Ms. Yuki Fu
Tel: +8615716217387